Conventional central 8 areas with LCD screen - 2 Siren output - 2 alarm and fault outputs and 2 configurable relay outputs - Repeater output - Up to 30 detectors per zone - End-of-line resistance auto detection
€188.00
Tax included
Reference DMT-FP9000-8-PT
Brand Dmtech
Quantity
Out-of-Stock

Free shipping

You might also like

  • DMTECH
  • Conventional fire alarm panel of 8 zones
  • Certificate EN54-2 and EN54-4
  • 2 independent siren outputs
  • 2 auxiliary alarm and fault outputs
  • 2 configurable relay outputs
  • Individual output for repeaters
  • Capacity for 2 12V batteries
  • 4 access levels ((3 user and 1 manufacturer)
  • LCD display with menu for advanced programming

Features

  • Conventional central 8 areas with LCD screen
  • 2 Siren output
  • 2 alarm and fault outputs and 2 configurable relay outputs
  • Repeater output
  • Up to 30 detectors per zone
  • End-of-line resistance auto detection

Specs

Primary power supplySwitching source 187-252V AC 50-60 Hz 65W max.
Backup power supply2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration.
Available languagesSpanish, English, Portuguese, Italian, French, and German.
Number of zones8 zones, up to 30 detectors by area.
Siren outputs2 siren outputs 24VDC. Independent and monitored open collector outputs
Relay outputs4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max.
End of line resistanceAreas fully monitored by end-of-line resistance (4.7K)
Auxiliary Output Voltage24VDC. Protected by resettable electronic fuse 1.85A
Protection IndexIP30
Temperature-5ºC~+45ºC
Material and colourABS, colour: White
Dimensions310 x 240 x 80 mm
Weight1,3Kg
Recommended cableFire cable with a minimum section of 1.0mm (18AWG).

Package content

  • Panels
  • Battery cables
  • Fusible
  • End of line resistors
Dmtech

Data sheet

Weight
1,3Kg
LED indicators
22 red (1 x fire, 1 x more alarms, 20 x programmable zone), 1 green (power), 13 amber and 12 bicolor (fault and system)
Dimensions
189mm (H) x 97mm (W) x 31mm (D)
310 x 240 x 80 mm
Material
Stainless steel
Mounting
Surface
Temperature
-5ºC~+45ºC
Primary power supply
Switching source 187-252V AC 50-60 Hz 65W max.
Backup power supply
2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration.
Number of zones
8 zones, up to 30 detectors by area.
2000 (200 per panel)
Siren outputs
2 siren outputs 24VDC. Independent and monitored open collector outputs
Relay outputs
4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max.
End of line resistance
Areas fully monitored by end-of-line resistance (4.7K)
Auxiliary Output Voltage
24VDC. Protected by resettable electronic fuse 1.85A
Protection Index
IP30
Material and colour
ABS, colour: White
Recommended cable
Fire cable with a minimum section of 1.0mm (18AWG).
Display
240 x 64 white backlit LCD screen.
Protocols
Argus Vega (preinstalled), Apollo (XP95 / Discovery), Hochiki ESP and Nittan Evolution
Available languages
Spanish, English, Portuguese, Italian, French, and German.
Core technology
Dual flash-based processors with real-time clock, diagnostics, programmable languages and character sets
Controls
Alphanumeric keypad that allows navigation, Reset, Mute buzzer, Mute sirens, Resonate, Evacuate and x4 programmable push-buttons
Number of loops
2 expandable to 4
Loop devices
240 in Argus Vega protocol (pre-installed), in the others it depends on the protocol
Loop
500mA
Siren outputs on plate
4 x 1 Programmable Amp
Relay outputs on plate
2 x 1 Amp 30v AC/DC programable(10mA, 5v min) - expandable to 4
Auxiliary output
24V 500mA
Programmable inputs
1 x programmable supervised input in plate
Programmable key switch inputs
8 x Free voltage input
Total output current available
5A maximum available for loop current + siren outputs + auxiliary power
Main power supply
200 - 240v 47-63 Hz AC (+10%, -15% tolerance) 1.4A Max
Charger current
2A with temperature compensation
Serial port interface
1 x in plate, connection for PC RS232, modem, IP, or portable printer
USB interface
1 x USB Type B for PC connection
Program
Keypad and LCD (built-in) or PC with Windows software
Event Buffer
5000 for events and diagnosis + 500 fires
Networks
Optional network card (ADV-MXP-503 - standard, or ADV-MXP-509 - fault tolerant)
Printer (optional)
In plate (only in the M, L, D boxes)
Box / Color
Steel IP30 / RAL7035
Metalwork Options
Flush Mount Bezel, Battery Box, Special Utility Boxes, Termination Boxes and Rack Mount Profile
Dimensions (H x W x D mm)
Standard: 475 x 450 x 120 Large: 475 x 450 x 190 Big Deep: 750 x 450 x 190
Battery capacity (Min - Max)
Standard: 24V 4Ah - 24V 18Ah Large: 24V 4Ah - 24V 45Ah Big Deep: 24V 4Ah - 24V 45Ah
Cable entry (20mm knockouts)
Standard: 19 x above, 11 x rear and 2 x below Large: 30 x above, 11 x rear and 3 x below Big Deep: 30 x above, 6 x rear and 3 x below